- LCD display
- Ambient temperature & humidity monitoring and water-leakage detection
- Digital & analog input/output contacts for monitoring and controlling other devices
- Supports SNMP communications protocol
- InsightPower Manager software for remote monitoring and recording
Specifications
Model
EMS1000 / EMS1100 / EMS1200
Input
EMS2000 Delta-BUS or SNMP Card: 12 Vdc (pin 1 & 4) with PDU SNMP card: 5Vdc (pin 2 & 4)
Input/Output
ContactsEMS1000 : 4 inputs (dry/wet)
EMS1100 : 4 digital outputs
EMS1200 : 2 analog inputs, 1 analog output and 1 water-leakage detection.
Dimensions (W x D x H) : 66 x 33 x 103 mm
Weight
EMS1000 : 120g
EMS1100 / EMS1200 : 130g
Temperature
± 0.4°C @ 0°C ~ 60°C
Humidity accuracy
±3% RH @ 0~80% RH